49
CVM
k
2
CONFIGURATION
4.7.2.1.a Digital input codes
CARD POSITION VARIABLE SYMBOL CODE MODUS ADDRESS
CARD 1
Input 1 meter IN_1001 400 0C80-0C81
Input 2 meter IN_1002 401 0C82-0C83
Input 3 meter IN_1003 402 0C84-0C85
Input 4 meter IN_1004 403 0C86-0C87
Input 5 meter IN_1005 404 0C88-0C89
Input 6 meter IN_1006 405 0C8A-0C8B
Input 7 meter IN_1007 406 0C8C-0C8D
Input 8 meter IN_1008 407 0C8E-0C8F
CARD 2
Input 1 meter IN_2001 408 0C90-0C91
Input 2 meter IN_2002 409 0C92-0C93
Input 3 meter IN_2003 410 0C94-0C95
Input 4 meter IN_2004 411 0C96-0C97
Input 5 meter IN_2005 412 0C98-0C99
Input 6 meter IN_2006 413 0C9A-0C9B
Input 7 meter IN_2007 414 0C9C-0C9D
Input 8 meter IN_2008 415 0C9E-0C9F
CARD 3
Input 1 meter IN_3001 416 0CA0-0CA1
Input 2 meter IN_3002 417 0CA2-0CA3
Input 3 meter IN_3003 418 0CA4-0CA5
Input 4 meter IN_3004 419 0CA6-0CA7
Input 5 meter IN_3005 420 0CA8-0CA9
Input 6 meter IN_3006 421 0CAA-0CAB
Input 7 meter IN_3007 422 0CAC-0CAD
Input 8 meter IN_3008 423 0CAE-0CAF
From the alarm 16 conguration screen, the equation editor screen is accessed to activate the
expansion card's physical outputs by pressing again the F2 (Next) button. This card allows
conguring outputs 01 to 04.
It is possible to access the inputs configuration screen (section 4.7.2.3., Digital inputs
conguration) from any alarm screen by pressing IN (F1). It is also possible to access the
output equations conguration screen (section 4.7.2.2. Relay output conguration) by pressing
EQ (F3).
To congure the expansion card outputs, enter the corresponding input code. The code that
corresponds to each input depends on the input number to be selected and the position in
which the card is inserted (see attached table).