WARNING: The value 00 in an outputs activation equation means that nothing at
all should be done. Thus, it should only be entered at the end of the equation. If
the value 00 is entered at the beginning of the equation, the CVMk2 will not make
the calculation or activate the corresponding output.
4.7.1.3. Digital inputs conguration
The card inputs are also congured in two different ways depending on whether the user
desires to congure the input as an incremental counter or a two-state logic input (ON/OFF).
size = 0000
Accordingly, the input is congured as a two-state input, ON/OFF. When the input is congured
as ON/OFF, it is not necessary to congure the next menu option, Dec. pos.
size 0000
When an input size other than zero is congured, this is congured as an incremental pulse
counter, which can have a maximum counter value of 10M. The value to enter is the multiplier
for each input pulse.
Dec. pos: Indicate the decimal positions that the corresponding input counter should
have.
The options available in the lower menu include:
Next(F2). This increases the input number from 1 to a maximum of 08 to access its
conguration. From the 08 input conguration screen, pressing F2 (Next) again
will take the user back to the 01 input conguration screen.
OUT (F1): Press this button to access the alarms conguration screen, Section 4.7.1.1.
To store the modied parameters in memory, press SET and conrm with OK (F4). To exit without
saving changes press ESC (F3).