2
CONFIGURATION
demand.: Zero the maximum demand values, including those for different tariff.
ext. cont.: Zero accumulated pulse values for the inputs from all static digital input
expansion cards.
4.6 COMMUNICATIONS
To access the CVMk2 communications conguration, select Setup inside the Menu.
Once inside the conguration menu, select ComM and press SET to enter the menu. In this
screen, congure the COM2 port to communicate the analyzer with the master PC or PLC.
The following entries can be edited in this menu:
Periph. no.: Peripheral number to be assigned to the device. The value should be
between 1 and 255.
bauds: Communication speed assigned to the COM2 serial port. The speeds that can
be congured are: 9600, 19200, 38400 or 57600 bps.
parity: Choose between NO, EVEN, ODD.
data bit: 8; this cannot be modied (in Modbus/RTU protocol).
stop bit: It is possible to choose 1 or 2.
protocol: MODBUS; this cannot be modied.
The communications parameters set in this screen are for the measurement
module. The baudarte congured in that menu affect to the serial COM2 port
and the ethernet communications. In case of communicate through ethernet
expansion card o ethernet converter, the baudrate congured in that menu has
to be the same than congured in XPORT of the ethernet expansion card o TCP
2RS converter