Circutor CVMk2 Series Manuale Utente Pagina 20

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 152
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 19
20
CVM
k
2
INSTALLATION
TERMINAL DESCRIPTION
1 Current transformer, L1 phase S1 connection
2 Current transformer, L1 phase S2 connection
3 Current transformer, L2 phase S1 connection
4 Current transformer, L2 phase S2 connection
5 Current transformer, L3 phase S1 connection
6 Current transformer, L3 phase S2 connection
7 Current transformer, neutral line S1 connection
8 Current transformer, neutral line S2 connection
9 L1 phase voltage input
10 L2 phase voltage input
11 L3 phase voltage input
12 Input voltage V
REF
(GND)
13 Input voltage NEUTRAL LINE
2.5.1 TAG FOR VOLTAGE AND CT CONNECTIONS
Product to be protected by an external fuse, model KTK-1 by
Bussmann, or similar, rated 600V, 1A. It should be provided with a
MCCB or equivalent device to switch off the system from the power
supply circuit. The power supply and voltage measuring circuit is
connected with cable minimum cross section of 1 mm
2
(AWG 17). The
current transformer secondary side connection line should have a
minimum cross section of 2 mm
2
(AWG 14 Cu) and with a minimum
temperature rating of 60 ºC.
2.5.2 POWER SUPPLY AND COMMUNICATIONS TAG
2.5 TERMINALS DESCRIPTION
Vedere la pagina 19