5�20�-VOLTAGEALARMS
Inthispointthephase-phasevoltagethresholds
abovewhichtheovervoltagealarm(E05)andthe
novoltagealarm(E06)shouldbetriggeredcanbe
configured�
Thealarmmustbeenabled(5�19�- ENABLING
ALARMS”
Pressthe keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Inordertoavoidpossiblefalseactivationsofsaidalarms,theyhaveapredefineddelayof5
seconds�
Theparameterstobeconfiguredare:
Thevalue of the overvoltage alarm: HI
Thevalue of the no voltage alarm: LO
Whenanyofthetwoalarmsaretriggered,theunitenterstheDisconnectionstatusand
disconnectsallthestages�Theunitdoesnotreturntoitsnormaloperatingstatusuntilthe
causeforthealarmdisappears�
The keyincreasesthedigitvalue�
The keydecreasesthedigitvalue�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay
Overvoltage alarm:
Maximum value: 99999V
Minimum value: 0V
No voltage alarm:
Maximum value: 99999V
Minimum value: 0V
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,5�27�-
SIMULATION SCREEN
94