
Active alarms Parameters
Active alarm code E01 to E017
(Table 9)
Iftherearemore than 4 alarms,the
informationisscrolledonthescreen�
Table 9: Alarm codes�
Code Description
E01
No current�Theloadcurrentislowerthantheminimumvalueorsomeofthe
currenttransformers(CT)arenotconnected�
Itisactivatedwhenthesecondarycurrentofthetransformerislowerthan50
mAinsomeofthephases�
Theunitdisconnectsthecapacitorsautomatically�
E02
Overcompensation�Theunitmeasurescapacitivepowerbutallthestages
aredisconnected�
ThiscanbeduetoanincorrectadjustmentoftheC/Kparameter�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof90
seconds�
E03
Undercompensation�Theunitmeasuresinductivepowerbutallthestages
aredisconnected�
ThiscanbeduetoanincorrectadjustmentoftheC/Kparameter�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof90
seconds�
E04
Overcurrent�Themeasuredcurrentexceedsthenominalcurrentby+20%
insomeofthephases�ThenominalcurrentisconsideredtobethatoftheCT
primary�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof5
seconds�
E05
Overvoltage�Thevoltagemeasuredinsomeofthephasesexceedsthecon-
guredvoltage(Vp-n)�
Theunitdisconnectsthecapacitorsautomatically�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof5
seconds�
E06
Low voltage�Thevoltageinsomeofthephasesislowerthanthecongured
voltage(Vp-n)�
Theunitdisconnectsthecapacitorsautomatically�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof5
seconds�
E07
Cos φ alarm�Thethree-phasecos φ islowerthanthelimitconguredinthe
Cosφalarm�Also,themeasuredcurrentsshouldbehigherthanthecongured
threshold�
Inordertoavoidpossiblefalseactions,thisalarmhasapredeneddelayof15
seconds�
41
Instruction Manual
Computer SMART III FAST
Commenti su questo manuale