Instruction Manual 1 LV CAPACITOR BANKS WITH DETUNED FILTERS OPERATED BY CONTACTORS FR SERIES INSTRUC
Instruction Manual 8 • FR filter bank with an auxiliary voltage obtained from an internal AUTOTRANSFORMER
Instruction Manual 9 Fig. 5-3 .- Installation of the current transformer (TC) (e
Instruction Manual 10 6 START-UP OF A CAPACITOR BANK WITH DETUNED FILTERS 6.1 Before start-up Automat
Instruction Manual 11 • Once ensured that the regulator is properly connected, adjust the regulator parameters for
Instruction Manual 12 • Keep the capacitor terminals and reactors clean. • Verify the state of the contac
Instruction Manual 13 Table 7-2.- Tightening torques of the cables to contact terminals MODEL Auxiliary (Nm) PO
Instruction Manual 14 7.2.4 Key points for inspecting capacitors. • Inspect the cables and terminals. The
Instruction Manual 15 Table 7-5.- Nominal consumption of the LC steps of an FR filter, depending on its power CURRE
Instruction Manual 16 8 GUARANTEE, CIRCUTOR guarantees its products against any manufacturing
Instruction Manual 17 9.1 Declaration of conformity
Instruction Manual 2 SYMBOLS AND WARNINGS Pay attention to the warnings in this manual, which
Instruction Manual 1 TABLE OF CONTENTS 1 INTRODUCTION ...
Instruction Manual 2 1 INTRODUCTION The purpose of this manual is to assist during the installation, s
Instruction Manual 3 3 RECEPTION, TRANSPORT, HANDLING AND STORAGE 3.1 Reception protocol Make sure that the
Instruction Manual 4 Fig. 3-2 .-Unloading with a Forklift 3.3 Storage The following storage recommend
Instruction Manual 5 - Current Transformer Input: 5 A , (Transformer In/5A) NOTE: Minimum cable section
Instruction Manual 6 4.6 Filter bank components Fig. 4-3 shows the different models of filter ban
Instruction Manual 7 5.2 Installation location It is important to maintain a minimum distance around the equipment t