5�3�-TARGETCOSφ
Thecosφmakesitpossibletodefinethepower
factorrequiredfortheinstallation�TheComputer
SMART III FASTwilladdthenumberofcapacitors
neededtoadjustthevalueascloseaspossible
totheobjectivevalue�Sincetheregulationisby
stages,itdoesnot performanyoperationsuntilthe
uncompensateddemandisatleast70%ofthe
powerofthesmalleststageorthecompensation
surplusis70%ofthepowerofthesmalleststage�
Fourtargetcosinescanbecongured,dependingonthestatusofthedigitalinputs(See “4�7�-
INPUTS”)theunitallowsoneofthe4programmedcosines�
Foreverycosine,youmustprogramthevalueandstatewhetheritisinductiveLorcapacitive
C�
Pressthe keytoentereditingmode�Itisidentifiedbythe symbolandtheblinking
ofthedigitstobemodified�
The keyincreasesthedigitvalueorshowsthenextoption�
The keydecreasesthedigitvalueorshowsthenextoption�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay�
Maximum value: 1�00�
Minimum value: 0�80�
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Presskey toaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,“5�27�-
SIMULATION SCREEN”�
76
Computer SMART III FAST
Instruction Manual
Commenti su questo manuale