3�5�4�- 3 voltages + Neutral and 1 current, Computer SMART III FAST 12 model�
Connectiontype:3U1C
VLN
IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1
P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
Power Supply
COM 1 2 3 4 5 6 7 8 9 10 11 12
COM
ACT C1...C12
Power Supply
Figure 6: 3 voltages + Neutral and 1 current, Computer SMART III FAST 12 model�
NB: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
NB: The auxiliary power supply can be connected Phase-Neutral (as in Figure 6)orPhase-
Phase,aslongasthepowersupplyrangeisnotexceeded(see"6�- TECHNICAL FEATURES)�
NB: In this type of connection, the connection from Neutral to V
LN
is not mandatory.
NB: In this type of connection, the current transformer must be connected to the IL1 termi-
nals.