Table 24:Modbus memory map: programming variables (Table 10)
C/K factor
Configuration variable Address Valid data margin Default value
C/Kfactor 1138 0-100(Valuex100) 100
Table 25:Modbus memory map: programming variables (Table 11)
Program
Configuration variable Address Valid data margin Default value
Program 1139 1111-1999 1111
Operationtype 113A 0(FCP),1(Total),2(Sim) 0
Table 26:Modbus memory map: programming variables (Table 12)
No� of stages
Configuration variable Address Valid data margin Default value
No�ofstages 113B
0-6(ComputerSMARTIIIFAST6)
0-12(ComputerSMARTIIIFAST12)
6
12
Table 27:Modbus memory map: programming variables (Table 13)
Connection and reconnection time
Configuration variable Address Valid data margin Default value
Connectiontime 113C 0-999networkcycles 10
Reconnectiontime 113D 0-999networkcycles 50
Table 28:Modbus memory map: programming variables (Table 14)
Alarm: Voltage THD
Configuration variable Address Valid data margin Default value
LowValue 1140 0-100% 5
HiValue 1141 0-100% 10
Table 29:Modbus memory map: programming variables (Table 15)
Alarm: Current x I THD
Configuration variable Address Valid data margin Default value
LowValue 1142 0-100% 4
HiValue 1143 0-100% 5
Table 30:Modbus memory map: programming variables (Table 16)
Alarm: Temperature
Configuration variable Address Valid data margin Default value
LowValue 1144 0-80ºC 55
HiValue 1145 0-80ºC 70
Table 31:Modbus memory map: programming variables (Table 17)
Alarm: Leakage Current
Configuration variable Address Valid data margin Default value
Searchfortheresponsiblestage 1146 0(OFF),1(ON) 0
Value 1147 10-1000mA 300
Stagesenabled 1148 0(No),1(Yes) 0
Table 32:Modbus memory map: programming variables (Table 18)
Alarm: Cos φ
Configuration variable Address Valid data margin Default value
ValueofCosφ 1149 80-100(Valuex100) 95
Currentvalue 114A 0-9999A 20
TypeofCosφ 114B 0(Capacitive),1(Inductive) 1