Circutor CVM-C10 Series Manuale Utente Pagina 61

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 82
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 60
4.10.- COMMUNICATIONS
The CVM-C10 units have one RS-485 communications port.
The unit has as standard two communications protocols: MODBUS RTU ® and BACnet.
The protocol and conguration parameters are selected in the setup menu. (4.9.28. RS-485
communications: Protocol)
Note: BACnet protocol available in units with version 3.00 or higher.
4�10�1� CONNECTIONS
The RS -485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires),
with a maximum distance between the CVM-C10 and the master unit of 1200 metres.
A maximum of 32 CVM-C10 units can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter to establish the
communications with the master unit.
B ( - )
A ( + )
S
POWER SUPPLY
INPUTS
A(+) B(-)
GND
RS485
S1 S2
S1 S2
S1 S2
L1
P1 P2
L2
L3
300V
~
Ph-NPh-Ph
520V
~
NV
L3L2
V
L1
V
P1 P2
P1 P2
I1 I2
OUTPUTS
Rc R2 R1 Tc T2 T1
S0-
S0+ S0+
POWER SUPPLY
INPUTS
A(+) B(-)
GND
RS485
S1 S2
S1 S2
S1 S2
L1
P1 P2
L2
L3
300V
~
Ph-NPh-Ph
520V
~
NV
L3L2
V
L1
V
P1 P2
P1 P2
I1 I2
OUTPUTS
Rc R2 R1 Tc T2 T1
S0-
S0+ S0+
RS-232 / USB / Ethernet / Profibus ...
PC
RS-485
RS-485
RS-232
USB
Ethernet
Profibus
...
Figure 25: RS-485 Connection diagram�
61
Instruction Manual
CVM-C10
Vedere la pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 81 82

Commenti su questo manuale

Nessun commento