Programming the maximum value
The maximum value: the alarm is activated when this value is
exceeded.
Press key
for 3 seconds to edit the maximum value selection.
The prog icon will be displayed on the bottom of the screen.
To enter or modify the value, press the
key repeatedly,
increasing the value of the ashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
In the case of some parameters (Table 14), you can modify the position of the decimal point.
To do so, press key after modifying the last digit and the decimal point will start ashing.
Press key repeatedly to modify the position of the decimal point.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step
Table 14:Decimal point and units of the alarm parameters�
Types of parameters Units Decimal point
Voltage
2000 V
200.0 V
20.00 kV
2.000 kV
Programmable
Current A Programmable
Frequency Hz Fixed
Power kW Programmable
Power factor PF Fixed
Cosine φ φ Fixed
Maximum current demand A Programmable
Maximum power demand kW Programmable
THD % Fixed
Programming the minimum value
The minimum value: the alarm is activated below this value.
Press key
for 3 seconds to edit the minimum value selection.
The prog icon will be displayed on the bottom of the screen.
To enter or modify the value, press the
key repeatedly,
increasing the value of the ashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
50
CVM-C10
Instruction Manual