66
Table 13-1.- Connection of CPC3i to Computer plus
The connection diagrams of the complete unit are shown on Fig. 2 and 3.
Each CPC3i card of a static capacitor bank must be configured with a different address (1 to 16) for each
step, using a rotating ADJ switch with the CPC3i card.
CPC3i-xMRS
Mando RS485
0V
230V
400V
2G2
2K2
2G1
2K1
TR1
3G2
3K2
3G1
3K1
1K2
1G2
1G1
1K1
TP3
TP2 TP1
LED
PH3
LED
PH2
LED
PH1
SH
RS+
RS-
AL1
COM
JP1
LED
CPU
TEST
0
7
1
5
3
1
1
1
2
4
5
6
8
9
1
0
1
2
1
3
1
4
ADJ
A B C D E F G
Fig. 121.- Terminals of the CPC3i-xRS card
Fig. 122.- Terminals of card A of Computer plus
13.1 MODBUS Control frame
Computer plus controls the CPC3i cards with the MODBUS protocol. In particular, it sends a frame every
20 ms, using the 15 function (N bits write). The message is a "broadcast" message, i.e., it will be read by all
cards, in any address. The format of the frame is as shown on Fig. 123.
The message is composed of a frame sent to the slave address 00H (broadcast, i.e., all CPC3i cards receive
all frames). The 1r bit address on the CPC3i card is 00H – 64H and the frame has 64 bits (00H – 40H),
grouped in 8 octets.