Circutor computer PLUS-TF Series Manuale Utente Pagina 63

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 69
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 62
63
12.1 Opening the Test menu
To open the test menu, go to the main menu (Fig.113). Use the arrows to select
the folder and press OK. A list with the three options available will be displayed (Fig.114).
Fig. 113.- Main menu
Fig. 114.- Options of the Test menu
The options can be selected with the and dynamic keys; then press OK.
12.2 Test cos and resonance test
These two options must be used at the same time. The purpose is to execute the manual connection and
disconnection of capacitors while displaying the cos or THDV and THDI of each phase. This allows you to
check that the compensation unit is working correctly and whether the connection of a certain number of
capacitors is causing resonances in the installation or not. Each test is carried out as follows:
The Test cos φ option of Computer Plus shows the cos φ of all phases and the type (inductive or
capacitive), as well as the cos φ III (total) and its type (Fig.115).
Fig. 115.- cos φ Test
Fig. 116.- Resonance Test
Vedere la pagina 62