User Manual Page 31 of 58
8.1 Power control parameters
The power control configuration parameters are shown in the following menu (Fig.8-1),
explained in detail below.
Fig.8-1 . Power control parameters to be configured
8.1.1 General
Fig.8-2 . General parameters configuration screen
Integration period (minutes): Configure the time in minutes of the energy values
integration window. After this time, the calculation will return to zero.
Instantaneous value: You need to enter an incremental energy variable or incremental
energy impulse meter. You can use the help button to enter a unit's energy variable, an
impulse meter or a formula whose result is an incremental energy value .
External synchronisation: In general, all billing meters have a sync output. This output
is used so that other units that measure the installation's electrical parameters do so in
Vedere la pagina 30