----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 39
- For passing to the next option, press "display": the setup for the second output
will appear (only if this output is available).
dA 2 OUTPUT D/A Nr.2
code
xxxx
Proceed as in the previous sections.
1.- Output calculation:
).(
)20(
Re
OffsetscaleF
Zero
solution
=
Offset & f. scale = defined by the user
Zero = 0 mA or 4 mA
()
ZeroOffsetMesuresolutionmA += *Re
mV = mA x ohms mV
(100 ohms)
= mA x 100
- Maximum load is of 500 (10 V - 20 mA)
Output of the power factor parameter ( PF):
0/4 mA ----------------------------------------------------- 20 mA
+0.00 Ind. / 1.00 / Cap. – 0.00
ó
–0.00 Cap. / 1.00 / Ind. + 0.00
Vedere la pagina 39