4.4.- TARIFFS
The CVM-C5 has two tariffs, T1 and T2, which can be selected through a digital input.
The selected tariff is determined based on the status of the input, as shown in Table 8.
Table 8: Tariff selection�
Tariff Digital input
T1 0
T2 1
The symbols T1 and T2 that appear on the display in the consumption data area indicate the
selected tariff and the tariff being shown according to Table 9�
Table 9: Displaying tariffs on the display
Symbol Display Selected tariff
T1 ashing Tariff 1 Tariff 1
T1 ashing
T2 steady
Tariff 2 Tariff 1
T1 ashing Tariff 2 Tariff 2
T2 ashing
T1 steady
Tariff 1 Tariff 2
4.5.- DIGITAL OUTPUT
The unit has an optoisolated NPN transistor (terminals 3 and 4 of Figure 1) that may be pro-
grammed as:
A pulse output by kWh or kvarh�
An alarm associated with a measurement parameter.
4.6.- PROGRAMMING
From the programming menu you can:
Dene the transformation ratios.
Program the ratio of kgCO
2
carbon emissions of the two tariffs.
Program the cost ratio of the two tariffs.
Program the maximum demand parameters.
Delete the energy meters and the maximum and minimum values.
Modify the display's backlight.
Program the digital output.
The CVM-C5 does not record programming changes until the programming is complete. If
the unit is RESET before nishing the programming or no key is pressed for 30 seconds, the
conguration will not be stored in the memory.
The CVM-C5 does not take any measurements during programming.
To enter the programming menu press the key for 3 seconds.
And press to access the rst programming point.
24
CVM-C5
Instruction Manual