3.3.- CONNECTION,REC 3 2 poles y REC 3C 2 poles
The REC 3 must be connected to a power circuit protected with miniature circuit breakers, in
accordance with its power supply range and consumption. In turn, the power circuit must be
ttedwithacircuitbreakerswitchoranequivalentdeviceinordertobeabletodisconnectthe
unit from the power supply mains.
In single-phase installations (phase and neutral, L and N), the supply cables are connected up
top and the cables from the protected loads are connected below.
The system will not work if they are wired in reverse order.
-25
F
N
LOAD
AUTO
POW ER
230V 50Hz
5VA
~;
REC
EN 50557
REC3
ON OFF
Figure 7: Connection diagram for : REC 3 2 poles and REC 3C 2 poles�
Note: Cross-section of the cable: 16 - 25mm
2
Terminals, opening covers or removing elements can expose parts that are
hazardous to the touch while the unit is powered
If the REC 3 indicates a permanent failure (AUTO and REC LEDs are lit), you
must check the RCCB and the installation.
If the installation of the unit is done with the RCCB in the OFF state, when panel
receives voltage the unit will not activate the automatic reclosing system for sa-
fety reasons. The AUTO and REC LED turn on after a few seconds. A manual
reclosing of the system must be done on the panel with voltage.