with peripheral number 23 to generate pulses proportional to the energy measured by a
QNA500 module with peripheral number 22 with the use of a WEB server).
First, create the energy object in QNA500
Open the Configure Objects menu of the QNA500
Activate Digital Object 1
Active Checkbox: Enabled
Type: Energy + (
three-phase active energy)
Description: Active energy (
for example)
Send to: 23 (
peripheral number of the M-8IO)
Active: Enabled
Press the Update button
Return to the WEB server of the M-8IO module.
Select the new energy object from the list (
8 available): 1
Peripheral: 22
Energy object: 1 (
previously configured in the QNA500 8IO)
Description: Active energy (
for example)
Quantity: 1 (
this would generate 1 pulse every 1 W/h)
Units: W
T
ON: 10 (this time is multiplied x10ms, i.e., the minimum possible)
T
OFF: 10 (this time is multiplied x10ms, i.e., the minimum possible)
Hardware Output: 3 (
pulse output being activated)
Active Checkbox: Enabled